TM 9-2920-257-30&P
Table 2-1.
Generator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-4.
Shorted Negative Rectifier Test.
Step 6.
C h e c k f o r s h o r t e d n e g a t i v e r e c t i f i e r s . Connect
ohmmeter to each of the three negative rectifier
leads in accordance with figure 2-4.
I f the ohmmeter reading is less than 100,000
ohms , r e p l a c e d r i v e e n d h o u s i n g a s s e m b l y i n
a c c o r d a n c e with paragraph 3-3, and go to step 8.
2-6
|