TM 9-2920-257-30&P
Table 2-1.
Generator Troubleshooting - continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Open Negative Rectifier Test.
Figure 2-5.
C h e c k f o r o p e n n e g a t i v e r e c t i f i e r s . Connect
Step 7.
o h n t m e t e r to each of the three negative rectifier
leads in accordance with figure 2-5.
I f the ohmmeter reading is more than 100 ohms,
replace drive end housing assembly in
a c c o r d a n c e with paragraph 3-3, and go to step 8.
2-7
|