Table 2-2. Operator/Crew Preventative Maintenance Checks and Services
EQUIPMENT NOT READY/AVAILABLE
- BEFORE D - DURING A - AFTER W - WEEKLY M - MONTHLY Q - QUARTERLY S/A SEMI ANNUALLY AN - ANNUALLY
IF
T/A - TRIENNIALLY
ITEM
B
D
AWM
Q S/A AN T/A
ITEMS TO BE INSPECTED
CHECK FOR
ACTION
PMC
NMC
NUMBER
NOTE
During periods of extreme heat, fire extinguishers
may release a portion of their charge through the
discharge nozzles. Visually inspect nozzles for
evidence of discharge or leaks. Refer to Chapter
2, Section III, Para. 2-5.9.
NOTE
HALON 1301 is a CFC and must be properly
recovered. Releasing pressure from an
extinguisher must be done by a certified
contractor.
NOTE
The two (2) Halon 1301 fixed fire suppression
systems operate independently and service the
main engine room, bowthruster room, emergency
generator room and the paint locker. Each system
is designed to provide an adequate amount of fire
retardant material for the space protected.
Tighten mounting straps.
X
System Components
Check the system components to ensure that
accidental damage to equipment has not
occurred. Ensure cylinder straps are securely
mounted.
X
Distribution System
Check for obstructions to the overhead discharge Remove obstructions.
nozzles.
X
Egress and Control Boxes
Ensure that egress to the extinguisher assembly
Refer to unit maintenance.
and all control pull boxes are unobstructed.
X
Pressure Gauges
Check extinguisher assembly for proper operating Troubleshoot, repair, or
Operating pressures
refer to higher level of
below 200 PSI or
pressure between 200 to 600 PSI.
maintenance.
above 600 PSI.
LSV PMCS
Change 12
2-260