TM 9-2920-257-30&P
Table 2-1.
Generator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-10.
S h o r t e d Printed Circuit Panel Assembly Capacitor Check.
Step 12.
Check for shorted or high leakage capacitors
b e t w e e n field negative and ground according to
NOTE
O h m m e t e r may deflect to low
r e s i s t a n c e reading momentarily and
then climb to a high resistance
r e a d i n g . T h i s is normal when
checking capacitors. T h e f i n a l
ohmmeter reading is to be used in
this test.
If ohmmeter reading is less than 100,000 ohms,
capacitors are shorted. Replace printed circuit panel
a s s e m b l y in accordance with paragraph 3-3 and go to
step 13.