Table 2-1.
Generator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-9.
S h o r t e d P r i n t e d C i r c u i t P a n e l A s s e m b l y Capacitor Check.
Step 11.
C h e c k f o r s h o r t e d o r h i g h l e a k a g e capacitors
between battery positive and field positive
according to figure 2-9.
NOTE
O h m m e t e r may deflect to low
r e s i s t a n c e reading momentarily and
t h e n climb to a high resistance
r e a d i n g . T h i s is normal when
checking capacitors. T h e f i n a l
o h m m e t e r reading is to be used in
this test.
I f ohmmeter reading is less than 100,000 ohms, capacitors
a r e s h o r t e d . R e p l a c e printed circuit panel assembly in
a c c o r d a n c e with paragraph 3-3 and go to step 13.