TM 9-2920-257-30&P
Table 2-1.
Generator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-2.
Shorted Positive Rectifier Test.
C h e c k f o r s h o r t e d p o s i t i v e r e c t i f i e r s . Connect
Step 4.
ohmmeter to each of the three positive rectifier
leads in accordance with figure 2-2.
I f the ohmmeter reading is less than 100,000
ohms, r e p l a c e d r i v e e n d h o u s i n g a s s e m b l y i n
a c c o r d a n c e with paragraph 3-3, and go to step 8.