Place the generator set control switch to the RUN position to start the generator set (FIGURE 3-29)-
FIGURE 3-29. Idle Position.
(3)
Observe the water temperature and oil pressure meter gauges and indicators for proper indications.
Coolant temperature must not exceed 1040C (2200F).Minimum oil pressure required are 10 psi at idle and
30 psi at full speed and load (FIGURE 3-30).
FIGURE 3-30. Off/Run Position.
(4)
Perform a visual inspection of the generator set while it is idling. Look for oil/water leaks and loose
connections (FIGURE 3-31).
FIGURE 3-31. Visual Inspection.