Table 3-1. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
AIR CONDITIONING - CONT
STEP 3.
Check for open contact on internal overload protector in compressor (A/C-1 and 3).
Allow time for compressor to cool and automatically reset. If it does not reset when cooled
down, do the following. Check for "open" or "short" in compressor (paragraph 2-15).
Replace as required (paragraph 3-25).
STEP 4.
Check for defective compressor or compressor motor.
a.
Test compressor or compressor motor for a "short" or "open" condition (paragraph 2-17).
b.
Replace defective compressor (paragraph 3-25).
11.
Compressor short cyles on high pressure cut-out.
STEP 1.
Check to see if high (discharge) pressure control (solenoid) is defective. Check for
defective control. Replace as required (paragraph 3-25).
12.
No cooling - blower does not run.
STEP 1.
Check to see if fan relay or capacitor is defective (A/C-1 and 3).
Replace relay or capacitor as required (paragraph 3-25).
STEP 2.
Check for defective fan motor. Replace fan motor (paragraph 3-25).
13.
No cooling - blower running.
STEP 1.
Check for defective run capacitor (self-contained units; A/C-1 and 3). Replace as required
14.
Partial or insufficient cooling - blower running.
STEP 1.
Check for low refrigerant charge. Find and repair leak (Malfunction 10). Evacuate and
recharge system with R-22 (paragraph 3-10).
STEP 2.
Check for air in system. Remove refrigerant, evacuate, and recharge with R-22 (paragraph
3-9
|