Table 3-1. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
AIR CONDITIONING - CONT
15.
Water leaking from unit.
STEP 1.
Check to see if condensate pump motor is running on self-contained units (A/C-1 and 3).
WARNING
Check motor for loose electrical connections.  Secure as
required. Check motor windings (paragraph 2-15). If "short" or
"open" in motor windings, replace defective motor or pump
assembly as required (paragraph 3-25).
STEP 2.
Check for defective impeller on condensate pump on self-contained units (A/C-1 and 3).
Check water in condensate drain pan. A defective pump impeller may cause the water to churn,
but will not empty from pan. Replace pump if impeller is defective (paragraph 3-25).
3-10