|
|
TM 55-1905-223-24-17
Table 3-1. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
AIR CONDITIONING - CONT
WARNING
Turn electrical power OFF.
(2)
With the unit shutdown, use the refrigerant gas leak detector in the refrigeration tool kit and
check all lines and components in the system for leaks.
NOTE
Leaks commonly occur in defective joints, fittings, gaskets, and in
breaks caused by vibration.
A portable gauge manifold must be hooked up on self- contained air
conditioners (A/C-1 and 3) to determine pressure.
(3)
If refrigerant has been lost due to a leak and pressure is below 175 psig, add enough R-22
refrigerant to system so that pressure is increased to 175 psig before checking for leaks
(Malfunction 8).
(4)
Locate leak and correct as required.
NOTE
Self-contained air conditioners (A/C-1 and 3) cannot be pumped down. The refrigerant
charge must be completely removed before opening the system for maintenance purge,
and recharged with new refrigerant before returning to normal operation (paragraph 3-10).
(5)
Remove the refrigerant charge as required by corrective action (Malfunction 5).
(6)
After corrective action is complete, add R-22 refrigerant (Malfunction 8) or evacuate and
recharge system (paragraph 3-10) as appropriate.
STEP 2. Check for defective transformer (A/C-1 and 3). Replace transformer (paragraph 3-25).
3-8
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |