Click here to make tpub.com your Home Page

Page Title: Table 3-1. Troubleshooting
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 55-1905-223-24-17
SYMPTOM INDEX - CONT
Troubleshooting
Procedure
Low suction pressure
Item 8
No cooling - blower does not run
Item 12
No cooling - blower running
Item 13
Partial or insufficient cooling - blower
Item 14
running
Water leaking from the unit
Item 15
Table 3-1 lists the common fault conditions that may be found during operation or maintenance of the
equipment. Look for causes and do corrective actions in the order listed. This manual cannot list every
symptom that may show up, and it cannot list all of the possible causes and corrective actions. If a symptom is
not listed, or if it keeps up after you have performed the corrective actions, notify your supervisor.
Table 3-1. Troubleshooting
Malfunction
Test or Inspection
Corrective Action
1.
No heat - fan/blower running.
STEP 1.
Check for open manual or automatic limit switch. Reset manual limit switch. If trips again,
check for defective manual and automatic limit switch. Replace as required (paragraphs 3-
12 and 3-13).
STEP 2.
Check for defective air flow switch on duct heaters. Check for air flow to heater. Replace
defective air flow switch as required (paragraphs 3-11 and 3-13).
2.
Not enough heat.
STEP 1.
Check for defective air flow switch. Replace as required (paragraphs 3-11 and 3-13).
STEP 2.
Check for element failure
a.
Clean and secure connections.
b.
Replace element (paragraph 3-16).
3-3

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business