TM 55-1905-223-24-17
3-13. Repair Heater, Duct Type, Stationary (Duct #4, #5, #6, #7, #8, #9, #10, #11, #12, #12A, #13, #14, #15,
#16). (FIGURE 3-4)
This task covers:
a. Repair
INITIAL SETUP :
Equipment Condition
Tools
Circuit breaker switched OFF, power
Tool kit, general mechanic's,
panel locked and tagged "Out of
Service - Do Not Operate."
Tool kit, electrician's,
See TM 55-1905-223-10 for HVAC systems
operation and equipment location.
Materials/Parts
Tags, Item 1, Appendix C
Manual limit capillary reset
P/N 41984011
Automatic limit capillary reset
P/N 50025003
Airflow switch P/N 51085002
Air probe P/N 41653001
Control contactor P/N 52332005
(Duct 8, 11)
REPAIR
WARNING
Make sure electrical power is OFF to avoid personal injury.
a.
Turn electrical power to heater (3) OFF and open terminal box door (7).
b.
Replace manual capillary reset (4) and/or automatic capillary reset (5):
(1)
Tag and disconnect electrical wiring from appropriate reset.
(2)
Remove mounting screws and remove reset.
(3)
Install new reset.
4)
Connect electrical wiring to proper terminal on reset.
3-24
|