TM 55-1730-226-13
Verify that the REGULATOR PRESSURE
1.
OUTLET VALVE (26) is fully closed by
turning the T-handle in a counterclockwise
direction.
2.
Verify that the BOTTLE PRESSURE OUTLET
V A L V E (31) is fully closed by turning the knob
in a clockwise direction.
3.
Unwind the filler hose (11) from its stowage
place in the stowage cover, remove the plastic
protectors (dust covers), and connect one end
to either the fitting on the BOTTLE PRESSURE
OUTLET VALVE or the fitting on the REGULA-
TOR PRESSURE OUTLET VALVE, as deisred.
4.
Attach the oxygen service fitting (40), which
is stored in the stowage cover, to the open end
of the filler hose.
OPERATION.
The Oxygen Servicing Unit is operated as follows:
3.3.1
Do n o t suddenly release the
o x y g e n . Extremes of pressure
differentials could damage
equipment.
Connect the valve on the desired oxygen bottle(s)
1.
by turning the knob in a counterclockwise direction
until fully open.
NOTE
Perform either Step 2 or 3, as
desired, depending upon whether
or not pressure regulation is re-
quired.
2.
Open the BOTTLE PRESSURE OUTLET VALVE
(31) by turning the knob in a counterclockwise
direction.
|