TM 9-6920-737-10
OVERNIGHT AND WEEKEND SHUTDOWN PROCEDURE
This procedure describes shutdown of the Shelter utility power to maintain emergency battery charging and limited air
conditioning for overnight and weekend periods.
1.
Make sure Electronic Equipment Power-Down Procedure has been erformed (see 2-199).
p
CAUTION
Never turn A/C MODE SELECTOR (2) to OFF unless there is a malfunction. Internal A/C protection heaters will be off
when MODE SELECTOR (2) is off.
2.
Obtain forecast of temperature ranges for the shutdown period. Review Chart (I) an set air conditioner controls
d
(2)and (3) for the average forecasted temperature range.
3.
Check HUMIDIFIER TANK WATER LEVEL windows (4) at each air conditioner to make sure they are filled.
Change 1 2-205
TM 9-6920-737-10
|