TM 9-6625-2803-14&P
3.0
AMMETER
TYPE - The Ammeter is of the moving iron type designed
3.1
for use with the current transformers contained in the Analyzer.
3.2
SCALES - The Ammeter has four full scale ampere ranges --
220, 110, 55 and 5.5 amps. The proper full scale value is
selected by connecting the load wires to the proper binding
posts.
3.3
PHASE SELECTION - The "Line Amps" switch is used to insert
(Neutral
the Ammeter into Phase A, Phase B, Phase C or Neutral.
is used for 30, 4-wire only).
3.4
POINTER LIFT - The Ammeter is equipped with a device to
lift the pointer from the zero position. This is controlled by
a knob on the front of the Ammeter. The pointer lifter is used
in determining motor starting currents. To do this, the pointer
is "lifted" to a position where it just barely moves when the
motor is started. This value of current so indicated is the
motor starting current.
ACCURACY - Ammeter indications, together with the trans-
3.5
former contained in the Analyzer, are correct within +/- 1% of
It reads RMS value of
the full scale value from 45 to 425Hz.
applied current.