TM 9-2920-252-34&P
d. Generator Electrical Resistance Checks. Make
all electrical resistance checks of generator's internal
circuits shown in Table 2-1. Figure 2-1 identifies the test
points listed in Table 2-1. If any resistance readings are
outside of limits given in Table 2-1, generator must be
repaired at the Depot level (refer to DMWR 9-2920-252).
NOTE
Circuit breaker must be closed (switch
lever at ON) for resistance checks.
Figure 2-1. Test Points for Generator
Resistance Checks
e. Regulator Electrical Resistance Checks. Make all
electrical resistance checks of voltage regulator's internal
circuit shown in Table 2-2. Figure 2-2 shows the location
of regulator test points used in Table 2-2. If any
resistance measurement is outside limits shown in the
table, regulator must be repaired at Depot level (refer to
DMWR 9-2920-252).
Figure 2-2. Test Points for Regulator
Resistance Checks