Click here to make tpub.com your Home Page

Page Title: Operate generator
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9- 2920- 224- 34&P
-
-
-
OPERATIONAL TESTING OF THE GENERATOR - CONTINUED
-
0011 00
NOTE
If at any time during these tests it is discovered that
sparking is in excess of conditions described, disconnect
generator from test stand and connect it for additional
run--in operations. Perform run--in operations for an
additional two to three hours to properly seat all brushes.
4) Operate generator (with voltage regulator connected) at 6500 rpm, 30 volts, and 300 amperes until frame
temperature shows no more than 2 F temperature rise in five minutes. Measure and record voltage
between field terminal "D" and main (negative) terminal "E". Also record condition of commutation and
total field current. Commutations should not exceed "pin--point" sparking with pin--points along trailing
edges of brushes only. Paralleling voltage (between terminals "D" and ME) must be between 1.2 and 1.4
volts dc, provided air inlet temperature is approximately 80 F. Higher or lower temperatures will affect
paralleling voltages.
5) Operate generator at 6500 rpm, 30 volts, and check for compounding at 0 (zero) amperes, 150 amperes,
and 300 amperes. Record field current and condition of commutation. If generator is properly
compounded, shunt field current (at terminal "A") will not exceed 3.0 amperes and field current will
increase with an increase in load. Conversely, field current will decrease with a decrease in load.
Commutation (sparking) must not exceed pin--points along trailing edge of brushes.
6) Reduce generator speed slightly below 1850 rpm, but not below 1600 rpm. Substitute a 1.25 ohm resistor
for voltage regulator in field circuit and stabilize generator output at 26 volts, 250 amperes until frame
temperature shows no more than a 2 F temperature rise in five minutes. Adjust generator speed to hold
voltage and current constant at these values. Record field current, speed, frame temperature, and
condition of commutation. The "come--in" speed of generator must not exceed 1850 rpm. Come--in should
occur at between 1600 and 1800 rpm, at 250 amperes.
7) Remove generator from test stand and blowout all dust from commutator area with compressed air.
CAUTION
Do not attempt any insulation strength test of tube axial
fan on generator (10889713). Damage to tube axial fan
would result.
8) Connect 250 volts, 60 cycle AC, for one minute between a ground on generator housing and terminals
"A", "B", and "D" in succession. This is for determining strength of insulation in generator field coil. There
must be no indication of breakdown during the test. If a breakdown should occur, which would be
indicated by smoke or arcing inside generator, defective components must be replaced. If replacements
are required, perform the entire test procedure after assembly.
9) Connect cooling--air tube axial fan motor to a 24--28 V dc power source, with an ammeter connected in
series with input supply.
10) Allow tube axial fan motor to run until warm and take an ammeter reading. The amperage draw should
not exceed 11.5 amperes at any time. If in excess of this value, it indicates a mechanical drag on motor
armature, fan impeller, or an electrical defect. Remove motor from test circuit and check for trouble.
Make necessary corrections and recheck as outlined in above instructions.
0011 00- 4
-

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business