Table 2-2. Operator/Crew Preventative Maintenance Checks and Services
EQUIPMENT NOT READY/AVAILABLE
- BEFORE D - DURING A - AFTER W - WEEKLY M - MONTHLY Q - QUARTERLY S/A SEMI ANNUALLY AN - ANNUALLY
IF
T/A - TRIENNIALLY
ITEM
B
D
AWM
Q S/A AN T/A
ITEMS TO BE INSPECTED
CHECK FOR
ACTION
PMC
NMC
NUMBER
X
Sacrificial anodes
Inspect all anodes
Replace as necessary.
58 cont
WARNING
Wear approved goggles, gloves, and apron. Avoid
contact with the skin, excessive inhalation of
vapor, or splashing in the eyes. In case of
emergency, flush affected area with water
immediately.
X
X
Chlorine Storage
Ensure the system has a continuous supply.
Add chlorine as necessary.
X
Solenoid Valves
Observe and listen to valves for proper operation. Repair/replace as
necessary.
X
Check valve for cleanliness.
Clean valve internally
X
Retention/reduction screen
Check screen for cleanliness.
Clean and flush screen
Surge Tank
X
X
X
Control Panel
Check for correct operating mode indicating lights. Troubleshoot, repair as
Perform control panel lamp test. Inspect and
necessary.
clean control panel.
X
Collection tank
Flush tank interior. Check low and high level
Repair/replace as
sensor operation.
necessary.
X
Inspect tank interior and exterior. Inspect level
Repair/replace as
sensors.
necessary. Clean level
sensors.
X
Electric motors
Inspect motors. Check exterior of motor, and
Clean exterior.
lubricate according to manufacturer's instructions. Repair/replace as
necessary.
LSV PMCS