TM 55-1915-200-10
B
Table 2-2. Operator/Crew Preventative Maintenance Checks and Services
EQUIPMENT NOT READY/AVAILABLE
- BEFORE D - DURING A - AFTER W - WEEKLY M - MONTHLY Q - QUARTERLY S/A SEMI ANNUALLY AN - ANNUALLY
IF
T/A - TRIENNIALLY
ITEM
B
D
AWM
Q S/A AN T/A
ITEMS TO BE INSPECTED
CHECK FOR
ACTION
PMC
NMC
NUMBER
X
Check fire pumps and sea chest valves for proper
Openings are
26
Fire Pumps
operation. Check fire pump supply line.
restricted to an extent
that normal operation
is hampered 50% or
more.
X
Check valves for proper alignment for system
27
Fire pump valve alignment
operation.
X
Visually inspect all accessible electrical cables,
Ensure connections and
Connections are
28
Electrical Wiring
connections and harnesses.
supports are secure, clean
damaged or
and undamaged.
contaminated.
WARNING
Do not smoke when observing battery electrolyte
level. Batteries give off fumes that can explode.
Electrolyte is an acid and can cause personal
injury if it comes in contact with the skin or eyes.
Wear approved goggles, gloves and apron.
X
Inspect batteries, terminals, cables, connections
Clean, add distilled water,
Unserviceable
29
Batteries, terminals and
and vent caps for tightness and cleanliness.
repair/replace as needed.
cables, caps, or
cables
Check liquid level.
terminals
X
Electrolyte
Check electrolyte level with hydrometer
If under standard, then
Low hydrometer
replace battery.
readings
X
X
Check battery chargers for proper connections to Tighten connections.
30
Battery Chargers
batteries, and correct DC output.
X
X
X
Visually inspect engine crankcases, oil filters,
Repair leaks.
Class III leaks
31
Engines, Reduction Gear
reduction gear and oil tanks for leaks. Direct
and Oil tanks
particular attention to all connections, sealing
joints and scuttle gaskets.
LSV PMCS