|
|
TM 55-1905-223-24-17
Table 4-1. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
AIR CONDITIONING - CONT
(2)
Make sure both handwheels on the manifold are closed fully clockwise.
(3)
Start and run compressor for 5 minutes before continuing.
NOTE
The sight glass in the liquid line will show a stream of bubbles, or a foamy
appearance, when the system is low on refrigerant.
(4)
Open the valve on the refrigerant container counterclockwise.
(5)
Open the suction service valve on the compressor three turns clockwise.
(6)
Watch the sight glass and slowly crack open the gauge port handwheel on the
combination (suction) gauge momentarily for 1 to 2 seconds, adding a small
amount of refrigerant. Close handwheel and observe sight glass condition.
(7)
If bubbles are still present, repeat cracking and closing combination with gauge
handwheel until sight glass shows a clear condition. Do not continue to add
refrigerant once the sight glass has cleared.
(8)
When sight glass has cleared, close (back-seat) service valve fully
counterclockwise.
(9)
Close valve on refrigerant container fully clockwise.
(10) Shut down compressor and disconnect gauge manifold from refrigerant
container and suction service valve.
STEP 2.
Check for clogged suction strainer in semi-hermetic type compressor (A/C-2).
Remove and clean suction strainer (paragraph 4-19).
7.
Compressor crankcase cold (sweating or frosting).
STEP 1.
Check to see if refrigerant is overcharged.
Remove excess refrigerant (Malfunction 3).
STEP 2.
Check to see if operating thermostat is set too low or is defective.
Adjust thermostat. Replace thermostat if defective (paragraph 4-14).
4-6
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |