TM 55-1905-223-24-17
3-23. Repair Fan, Ventilating (Exhaust Fan #3). (FIGURE 3-14)
This task covers:
a. Repair
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
Ventilating fan removed (para. 2-28).
See TM 55-1905-223-10 for HVAC systems
Materials/Parts
operation and equipment.
Tag, Item 1, Appendix C
Crocus cloth (fine),
Item 5, Appendix C
Impeller P/N 783076-51
REPAIR
WARNING
Make sure electrical power is OFF to avoid personal injury.
a. Remove impeller (3) from shaft of motor (2).
b. Check impeller (3) for bent or broken blades. Replace as required.
c.
Using drift pin, remove bushing (4) from impeller.
d. Sand the end of the motor shaft lightly with fine crocus cloth to remove dirt, grease, or corrosion.
e. Install bushing (4) in impeller (3).
f.
Install impeller onto shaft of motor (2).
g. Install ventilating fan (1) (paragraph 2-29).
h. Operational check:
(1)
Turn electrical power ON.
(2)
Start and run fan to check operation.
(3)
Remove "Out of Service" tag from circuit.
3-54
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |