2-29. Repair Motor, Electric, Alternating Current (Supply Fan #6)
This task covers:
a. Removal,
b. Repair,
c. Replacement.
INITIAL SETUP
Tools
Equipment Condition
Tool kit, general mechanic's
Circuit breaker switch OFF, power
panel locked and tagged "Out of
Tool kit, electrician's
Service - Do Not Operate."
Puller, 5120-00-516-3120
See TM 55-1905-223-10 for HVAC systems
operation and equipment location.
Materials/Parts
Tags, Item 1, Appendix C
Grease, Item 2, Appendix C
AC electric motor
P/N 35J790W321
Bearing P/N 205
Annular ball bearing P/N 203
WARNING
Make sure electrical power is OFF to avoid personal injury.
REMOVAL
a.
Remove weather cover from fan assembly for access to motor (paragraph 2-28).
b.
Tag and disconnect electrical wiring in motor terminal box (9, FIGURE 2-16).
c.
Refer to paragraph 2-28 and FIGURE 2-18, and remove the motor as follows:
(1)
Loosen tension on V-belt (8). Remove belt from around motor pulley (9, FIGURE 2-18).
(2)
Remove the motor pulley.
(3)
Remove motor mounting bolt, nut, and lockwasher assemblies (3).
(4)
Remove the motor (2) from the motor base (10).