TM 55-1905-223-24-17
3
In a single phase circuit, turn the power ON and check between A, and G (ground) with a
check between B1, and G. If no voltage is read, the B to B1 fuse is defective.
Figure 2-3. Checking Single Phase Circuit Fuses.
4
In a three phase circuit turn the power ON and check between A-C1, C-B1, and C-A1 with a
voltmeter (FIGURE 2-4). If no voltage:
A-C1 = blown C fuse.
C-B1 = blown B fuse.
C-A1 = blown A fuse.
Figure 2-4. Checking Three Phase Circuit Fuses.