TM 55-1905-223-24-17
Table 2-1. Preventive Maintenance Checks and Services (PMCS) - CONT
D - Daily
M - Monthly
B - Bimonthly S - Semiannually
A - Annually
Item
Intervals
Items To Be
No.
D
M
B
S
A
Inspected/Serviced
Procedures
13
All ventilation fan
WARNING
motors (SF and EF)
Turn electrical power OFF.
Secure electrical power and lubricate bearings with
one or two shots from a general purpose grease gun.
Refer to LO 55-1905-223-12.
14
All ventilation fan
WARNING
assemblies (SF and EF)
Turn electrical power OFF.
Secure electrical power and check all mounting
hardware for looseness. Secure all bolts, nuts,
and screws until snug.
Check all electrical connections for looseness.
Secure as required.
15
All V-belt drive pulleys
WARNING
(SF-4 and 6, EF-4 and 6,
A/C-2)
Turn electrical power OFF.
Secure electrical power. Remove V-belt and inspect
pulley sheave for burrs, chips, or cracks. Replace
pulley as required. Check for dirt, oil, rust, or
other foreign matter in the pulley groove. Remove
rust with a hard wire brush. Clean with rag and
soapy water.
2-15
|