TM 55-1905-223-24-17
Table 2-1. Preventive Maintenance Checks and Services (PMCS) - CONT
D - Daily
M - Monthly
B - Bimonthly S - Semiannually
A - Annually
Item
Intervals
Items To Be
No.
D
M
B
S
A
Inspected/Serviced
Procedures
9
Seawater condensers
Clean seawater strainer (TM 55-1905-223-24-18).
(A/C-l, 2, and 3)
10
All ventilation fans
WARNING
(SF and EF) and A/C-2
blower motor
Turn electrical power OFF.
Secure electrical power and lubricate the fan
bearings with one or two shots from a general
purpose grease gun. Refer to LO 55-1905-223-12.
11
Self-contained air
WARNING
conditioner fan motors
(A/C-1 and 3)
Turn electrical power OFF.
Secure electrical power and lubricate bearings with
six to eight drops of 20W oil applied into the oil
ports on the motor.
All heaters (DH, UH, and
WARNING
12
CH)
Turn electrical power OFF.
Secure electrical power to the heater and check all
electrical connections for looseness. Secure as
required.
2-14
|