Table 2-1. Preventive Maintenance Checks and Services (PMCS)-CONT
E - Every 20 hours
W - Weekly
Q - Quarterly
S - Semiannually
A - Annually
B - Biennially
ITEM
INTERVAL
ITEMS TO BE
Procedures
NO.
INSPECTED/SERVICED
EWQ
S
A
B
5.
Battery - CONT
d. Place the Emergency Generator Run-Off-Auto Switch to
CONT
Auto, and insure that the Emergency Stop PB Switch is Pulled out
6.
Oil filter
e. Place the Emergency Switchboard Mode Switch to Auto.
NOTE:
The Emergency System is now ready to energize the Emergency
Switchboard in case of a main switchboard power failure.
CAUTION
When testing, run the generator at
25% to 100% load. Extended operation
under very light or no load will
result in more frequent maintenance.
Check the specific gravity of the battery
electrolyte in each cell.
Remove the cell caps and check the electrolyte
level in each cell. Add distilled water as
required to bring the level to the split ring in
each cell. Refer to TM 55-1905-223-24-18.
Visually inspect the terminals for loose, broken,
or corroded connections.
a. Repair or replace broken cables or terminals (TM 55-1905-223-24-18).
b. On corroded terminals, remove the cables and
clean with a battery brush. Connect the cables and tighten.