|
|
TM 9- 2920- 224- 34&P
-
-
-
WATERPROOF TESTING OF THE GENERATOR - CONTINUED
-
0012 00
2. Test Procedure.
a. Open shutoff valve (6) to increase air pressure in outlet closure (2) (and in generator) to 6 in. Hg. (2.95 psi).
b. Close shutoff valve (6) and start timing at an interval of 2 1/2 minutes.
c.
At end of timed interval, pressure indicated on gage (4) shall be at least 2 in. Hg. (0.98 psi). If pressure is less
than 2 in. Hg (0.98 psi), excessive leakage is indicated.
CAUTION
Do not allow water to enter generator. Maintain positive
pressure to test setup whenever generator is lowered into
water.
d. If leakage is indicated, open valve (6) to restore 6 in. Hg (2.95 psi) and submerge generator with air--tight
closures in water dip tank. Note source(s) of air bubbles.
e. If source of leakage is at air--tight closures, this leakage must be stopped to obtain true leakage rate for
generator. Repeat steps a through c after leakage at air--tight closure has been stopped.
f.
When only source(s) of bubbles are on generator, remove air pressure and apply sealant externally at source
location(s). Allow sealant to set, then retest (steps a through c).
END OF TASK
0012 00- 2
-
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |