2-7.4.2. Bypass of 25-Second Discharge Delay.
e. If steering is not possible from the pilothouse,
dispatch a crew member to the Emergency Steering
System Station and establish communication on the
a. Pull out locking pin (3, FIGURE 2-225).
sound powered telephone system.
b. Pull lever to open.
f. Switch the Emergency Transfer selector (6,
FIGURE 2-223) located in the Emergency Steering
2-7.4.3. Manual Release of Halon for Fire in Bow
System Station, to #1 Emergency System position.
Thruster Room.
g. Attempt  to  steer  the  vessel  using  the
Emergency Steering Station joysticks (3 and 4, FIGURE
a. Close all doors to protected area.
2-224), at the direction of the helmsman.
b. Open 1/2" stop valve (1, FIGURE 2-226)
located in the STBD deck store, by operating release
2-7.4. Halon 1301 Fire System.
lever on top of valve. (Remove pin and pull lever.) c.
Open CO2 pilot cylinder (2) by operating release lever
2-7.4.1. Manual Release for Halon for Fire in Engine
on side of cylinder valve. (Remove pin and pull lever.)
Room.
NOTE Alarm siren will sound in Bow Thruster room and
discharge of Halon will be delayed 25 seconds to allow
evacuation of area to be protected.
a. Close all doors to protected area.
b. Open 1/2" stop valve (1, FIGURE 2-225),
WARNING
located in the machinery room, by operating release
Halon  1301  may  produce  toxic
lever on top of valve. (Remove pin and pull lever.) c.
byproducts while extinguishing fire.
Open C02 pilot cylinder by operating cylinder release
Where possible, the area in which
lever (2) on side of cylinder valve. (Remove pin and
the discharge took place should be
pull lever.)
left  secured  for  30  minutes.
Personnel should wear protective
NOTE
clothing and breathing apparatus
Alarm siren will sound in Engine
upon re-entry.
Room and discharge of Halon will be
delayed for 25 seconds to allow
2-7.4.4. Bypass of 25-Second Discharge Delay.
evacuation of area to be protected.
WARNING
a. Pull out locking pin (3).
Halon  1301  may  produce  toxic
b. Pull lever to open.
byproducts while extinguishing fire.
Where possible, the area in which
the  Halon  discharge  took  place
should be left secured for a minimum
of 30 minutes.  Personnel should
wear
protective
clothing
and
breathing apparatus upon reentry.
2-584