Halon 1301 Fire Suppression System
(4) Pull interior handle away from pull box
alarm. System discharges within 25
approximately 4 to 6 inches. Release handle.
seconds after avtivation. Evacuating
personnel must secure the door as
(5) Pull handle (2).
they evacuate the area.
(6) Pull down on handle and open cover on
a. Operation of the emergency generator room
CYLINDER RELEASE pull box using hammer (3).
surface pull box (FIGURE 2-143) will release Halon into
the actuation piping.
Halon is held back by the
(7) Pull interior handle away from pull box
discharge delay for 25 seconds while the siren sounds
approximately 4 to 6 inches. Release handle.
and pressure switches are activated for ventilation
shutdown.
NOTE
Alarm siren will sound in bow
b. After the Halon system has been discharged,
thruster room. Discharge of Halon
the pressure operated switch mounted in upper
will be delayed for 25 seconds to
machinery room must be reset by pushing the stem
allow evacuation of bow thruster
down to the SET position (FIGURE 2-142).
room.
Discharge of Halon is
completed in 10 seconds.
NOTE
Pressure Operated Switches Reset.
Further resetting is not rerequired.
During the 25 second warning time,
The Halon cylinder must be
two
PRESSURE
OPERATED
recharged or replaced and the pull
SWITCHES
automatically
shut
box must be reset by depot
down the bow thruster engine and
maintenance when the vessel is
the ventilation system in the bow
docked.
thruster room.
Before this
equipment can be restarted, the
2-5.9.4. Paint Locker Halon Operation.
two
PRESSURE
OPERATED
SWITCHES must be reset.
a. A Halon fire suppression cylinder is mounted in
the rear of the paint locker above the top shelf.
(8) Push the stem (1, FIGURE 2-143) down
to the SET position.
WARNING
NOTE
All personnel shall leave the paint
Further resetting is not required.
locker
area
immediately
upon
The Halon and C02 cylinders must be
activation of the Halon 1301 Fire
recharged or replaced and the pull
Suppression System.
System
boxes must be reset by depot
discharges within 10 seconds after
maintenance when the vessel is
activation.
Evacuating personnel
docked.
shall secure the watertight door as
they evacuate the area.
b. Cylinder is equipped
with
an
automatic
WARNING
temperature actuated valve.
All personnel shall leave the
emergency
generator
room
immediately upon activation of the
2-413
|