2-5.4.1.2. Heating/Air Conditioning Officer Staterooms.
(8) Press AIR CONDITIONING COOLING
WATER PUMP NO. 1 start button (114).
a. Select heat or cool mode (11, FIGURE 2-112,
Sheet 1 of 2), as necessary.
(9) Observe discharge pressure gauge (8,
b. Turn thermostat (12) to desired temperature.
NOTE
c. Turn fan selector (10) to high, medium, or low
If no pressure is indicated within 30
speed.
seconds, press stop button (113,
2-5.4.1.3. Heating/Air Conditioning Enlisted Staterooms
FIGURE 2-103, Sheet 6 of 7). Refer
and Pilothouse.
chilled  water  system  to  unit
a. Select heat or cool mode (9, FIGURE 2-112,
maintenance.
Sheet 1 of 2), as necessary.
c. Align chill water piping system (FIGURE 2-111)
b. Turn thermostat (8) to desired temperature.
as follows:
c. Turn fan selector (7) to high, medium, or low
(1) Open chill water circulating pump suction
speed.
valve (7).
2-5.4.1.4. Air Conditioning Control Room.
(2) Open pressure gauge cutout valve (4).
a. Turn thermostat (14, FIGURE 2-112, Sheet 2 of
2) to desired temperature.
(3) Open  chill  water  circulating  pump
discharge valve (1).
b. Turn fan selector (13) to high, medium, or low
speed.
(4) Open chill water discharge valve (9) from
chiller barrel.
2-5.4.1.5. Heater Operation.
a. Turn thermostat (15, FIGURE 2-112, Sheet 2 of
(5) Set circuit breaker (9, FIGURE 2-101,
2), to desired temperature.
Sheet 16 of 21) on P2 panel to the ON position.
b. Turn ON-OFF switch (16) to ON.
(6) Set chill water circulating pump OFF/ON
2-5.4.2. Potable Water System. (FIGURES 2-113 and
switch (2, FIGURE 2-111, Sheet 1 of 2) to ON position.
2-114)
(7) Observe pressure gauge (5, Sheet 1 of 2).
a. Close all valves in potable water piping system.
NOTE
If no pressure is indicated within 30
seconds, press OFF/ON switch (2,
FIGURE 2-112, Sheet 1 of 2) to OFF
position. Refer chill water circulating
pump to unit maintenance.