TM 55-1915-200-10
CAUTION
(4) Open port generator's fuel oil supply valve
If oil pressure does not rise to 45 PSI
(21).
within 15 seconds, stop engine or
(5) Open fuel oil filter inlet valve (20).
equipment  damage  could  result.
NOTE
Notify unit maintenance.
Place one fuel oil filter in operation
e. On Engine Room Console (FIGURE 2-106,
and keep the second as backup.
Sheet 5 of 12), press and hold PGE start pushbutton
(6) Open fuel oil filter outlet valve (18).
(47).
(7) Open fuel oil discharge valve to day tank.
NOTE
(8) Flood the Ship Service Diesel Generator
If engine fails to start within 30
fuel system by pumping the hand operated fuel oil
seconds,
release
the
starter
priming pump (14) until a slight pressure is indicated on
pushbutton. Wait 2 minutes to allow
the engine fuel pressure gauge (4, FIGURE 2-22).
the starter motor to cool before
c. Align Ship's Service Diesel Generator cooling
using it again.
water piping system (FIGURE 2-105) as follows:
f. Allow engine to run 3 to 5 minutes or until water
(1) Open port generator cooling water suction
temperature gauge (22, Sheet 4 of 12) begins to rise.
valve (31, Sheet 1 of 2) from keel cooler.
g. On Main Switchboard (FIGURE 2-102, Sheet 1
(2) Open cooling water discharge valve (25)
of 7) set selector switch (8) to GEN. NO. 1.
from expansion tank to generator.
h. Increase GEN.  No.  1 speed control (33) on
(3) Open  port  generator  cooling  water
main switchboard until hertz meter (7) reads 60.
discharge valve (22) to keel cooler.
i. Turn GEN.  1 BUS S.P.  switch (34) to read
NOTE
phase 1-2.
If ship's service diesel generators
j. Adjust GENERATOR NO.  1 VOLTAGE ADJ
require extra cooling, suction and
RHEO (26) to read 460 on A.C. VOLTS meter (1).
discharge valves (32 and 21) to
NOTE
cooling coils located in ballasts
If
generator
is
started
with
tanks may be opened.
MAN/OFF/AUTO  switch  (29)  in
d. On STBD side of electric start generator, twist
manual position, voltage adjustment
the kill pushbutton (7, FIGURE 2-22) clockwise to
is made by VOLTAGE switch (27).
ensure it is in the run position.
k. Set GENERATOR #1 CKT BKR (62, FIGURE 2-
102, Sheet 4 of 7), to ON position.
2-315