Table 2-1. Description of Operator's Controls and Indicators - CONT
Key
Control or Indicator
Function
Portable Fire Pump (FIGURE 2-47)
1
Pressure Gauge
Indicates pump pressure, or pump vacuum
when priming.
2
AMPERES Gauge
Indicates if alternator is charging or
3
OFF-START-RUN
Switch turns engine off in OFF, allows
engine to start in START, and allows
engine to run in RUN position and
prevents over speed of engine if prime
is lost.
4
PRIME
Pushbutton to put pump in priming mode.
5
START
Pushbutton to place engine in starting
mode with OFF-START-RUN switch in START
position.
6
CHOKE
Controls carburetor fuel/air mixture.
7
SPEED
Controls speed of engine.
8
Water Discharge Valve
In closed position and PRIME pushbutton
depressed, pump is in priming mode. In
open position, pump can discharge
water.
9
Pump Drain Valve
When open, drains water from pump.
10
Manual Priming Inlet Plug
To manually prime pump when lift is
greater than 20 feet.
11
Priming Pump Discharge Port
Discharges output of pump.
12
Manual Start Pull Cord
Provides emergency engine starting.
13
External Fuel Tank
Provides fuel for pump engine.
2-148