TM 55-1915-200-10
Table 2-1. Description of Operator's Controls and Indicators - CONT
Key
Control or Indicator
Function
Main Switchboard (FIGURE 2-19) - continued
14
GENERATOR NO. 2
Indicates (white light) power
POWER AVAILABLE
available from generator
number 2.
15
A.C.
Indicates undesired ground on
AMPERES
circuit, expressed in amperes.
TO GROUND
16
GRD DETECT
Tests AC amperes to ground meter.
PUSH TO TEST
Removes meter from circuit to
METER
check meter calibration.
17
VOLTAGE
Regulates voltage output for
generator number 2.
18
FLASH
Provides voltage until voltage
starts to build up in number 2
generator.
19
MAN-OFF-AUTO
Places number 2 generator voltage
regulator in MAN (manual) OFF, or AUTO
(automatic) position.
20
GEN 2
Increase or decrease speed of
SPEED CONTROL
diesel engine driving number 2
generator.
21
GENERATOR NO. 2
Adjusts output of generator
VOLTAGE ADJ RHEO
number 2 to output of generator
number 1 for parallel operation.
22
White Light Indicator
Indicates ground fault condition
on any of three phases of the shp's
i
voltage (generated or shore supplied).
23
PUSHBUTTON
Tests clear lights of three phases
of ship's voltage.
24
Synchro Indicator
Blinks (white light) at frequency
generator. Steady light indicates
generator number 2 in frequency
synchronization with generator number 1.
2-91
|