TM 55-1915-200-10
1-10.2.3.1. 30-ton R.L. Chiller Package Model LM2-
system.
A low pressure control switch stops the
WC30-6S. The chilled water package generates and
compressor in the event of low pressure in the low side
of the system.
distributes chilled water to all space air conditioning
units via the chilled water piping system. The chilled
1-10.2.3.5.
15-Ton Sea Water Condensers.
The
water package is a nominal 30-ton, dual circuit
refrigerant to cooling water plant designed for complete
condensers are heat exchangers in which the
automatic operation. The two refrigeration systems of
compressed high temperature refrigerant gas is lowered
the package comprise two compressors, two cleanable
in temperature and condensed to a liquid. Sea water is
sea water condensers, two individual sets of controls,
pumped through the tubes absorbing the heat given off
and one dual circuit liquid chiller barrel. The design of
by the refrigerant and then back overboard.
the package is such that mechanical or electrical failure
in one refrigerant circuit will not affect operation of the
1-10.2.3.6.
Water Regulating Valve.
The water
other circuit.
regulating valve automatically controls the sea water
flow through the condenser to maintain a relatively
1-10.2.3.2. 30-Ton Dual Circuit Chiller. The chiller
constant condensing pressure and temperature. This
circulates water to be cooled around refrigerant tubes for
valve is actuated by the refrigerant high (discharge)
cooling. The chiller is of the shell and tube type with two
pressure in the condenser and must be adjusted to
separate refrigerant circuits. Water to be cooled is
maintain the required condensing pressure and to
circulated through the shell and cold refrigerant flows
restrict water flow when the compressor is stopped. The
through the inner tubes. The fresh water system is
water regulating valve is located in the condenser sea
charged with a 35% (65 gallon) Ethylene Glycol mixture
water inlet line.
down to 0 . The approximate system total volume is
F
200 gallons of liquid. The hand valve is located on the
1-10.2.4. Model 39BA-050 Air Handling Unit. This air
suction side of the chilled water pump. By use of this
handling unit provides cooling, heating and positive
valve, some of the system mixture can be drawn off and
pressure for the galley and passageway areas of the
tested with a hydrometer. The systems solution is
officers deck, poop deck, bridge deck, and mezzanine
protected to 0 .
F
decks. The system passes outside air through the
chilled water coil using a continuously operating blower.
1-10.2.3.3.
15-Ton 460 Volt Compressor.
The
Chilled water at 40 is circulated through the coil from
F
the chiller package and reduces the 95 entering air to
F
compressor withdraws refrigerant gas from the
approximately 57 .
F
evaporator and delivers it to the condenser at an
increased temperature and pressure. This temperature
This conditioned air is then circulated through the duct
is such that refrigerant heat can be absorbed by sea
system.
water at ordinary temperatures. The drive motor turns
the compressor by means of a common crankshaft.
1-10.2.5. Model TFZU 22 kW Heater. The 22 kW
1-10.2.3.4. Control Box Assembly. The control box
heaters are duct mounted heating sources. The heaters
assembly controls and monitors chiller package
are controlled by two stage heating thermostats. The
operation. It contains starting controls and a high
first stage, 7 kW,
pressure control switch which stops the compressor in
the event of excessive pressure in the high side of the
1-75
|