TM 55-1905-223-24-4
REPAIR
Repair at this level of maintenance is by replacement of: Cable assembly (9), flow control thermostat (13), and heater
element (18).
REPLACEMENT
a.
Install flow control thermostat (13) and replace insulation sleeve (12), connector (11 and nonmetallic
)
grommets (10).
b.
Install flat washers (17) and heater element (18).
c.
Secure with hex head capscrew (19), 1ockwasher (15) and nut (16).
d.
Install cable assembly (9) on heater element (18) and secure with hex nuts (14).
e.
Position cable assembly (9) in J clamp (8) and secure with self-locking screw (7) and hex nut (6)
f.
Install cable locking ties (5).
g.
Replace grille (21) and secure with hex head capscrews (20).
h.
Replace front cover (3) and secure with hex head capscrews (4).
i.
Replace top cover (1) and secure with hex head capscrews (2).
j.
Restore power to emergency generator set, (TM 55-1905-223-10).