TM 55-1905-223-24-4
Table 2-2. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
f.
If any of the above checks indicates a faulty SCR module, replace module.
STEP 4.
Check for defective mini-bridge rectifier as follows:
a. Connect an ohmmeter from each AC terminal to (-) terminal. You should see low resistance in one
direction and high resistance in the other direction.
b.
Connect an ohmmeter from each AC terminal to (+) terminal. You should see low resistance in one
direction and high resistance in the other direction.
c.
If any of the above checks indicate a faulty rectifier. Replace rectifier. (Refer to TM 55-1905-223-24-18.)
14. Generator set output voltage high or low.
WARNING
Avoid electrical shock. Line voltage is present.
2-31
|