TM 55-1905-223-24-4
Table 2-2. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
STEP 7.
Check for shorted wires.
a.
Visually inspect for broken or bare wires.
b.
Unaccessible wires can be verified by checking for continuity between the wire and ground.
STEP 8.
Check for loose, broken or ground d wire to the remote start.
e
WARNING
To avoid electrical shock. Verify that the generator circuit
breaker is in the off position and the battery is disconnected.
a.
Remove the conduit box side covers and lid.
b.
Remove the regulator protective cover.
c.
Check for continuity between terminals 3 and 4.
STEP 9.
Check to see if solenoid or starting motor is malfunctioning.
Temporarily connect the starter solenoid terminals. If engine cranking
does not occur, replace the starter motor (para.2-20).
2. Engine cranks but will not start: no smoke from exhaust.
STEP 1.
Check to see if incorrect start/reset procedures were used. (RUN/OFF
switch must be in RUN position manual control only).
Use the, correct procedure.
STEP 2.
Check fuel level in supply tank.
Replenish supply.
STEP 3.
Check to see if fuel shutdown valve is closed. Check for loose wire and verify the valve is open.
a.
Remove the valve.
b.
Connect 12 Vdc to the terminal and ground the body.
c.
Observe plunger movement.
STEP 4.
Check to see if fuel filter is plugged, or contains water or other contamination (PMCS, Item 12).
2-21
|