|
|
TM 55-1905-223-24-17
(b) Connect the high pressure gauge (3, FIGURE 4-16) hoseline (5) to the gauge port
connection on the compressor discharge valve (1, FIGURE 4-17).
(c) Connect the common hoseline (6, FIGURE 4-16) to the suction connection (9,
(d) Connect the discharge line.(7) of the vacuum pump to an empty R-22 refrigerant
container (6). Make sure hand-wheel, gauge port, valves (1, 3) are closed by
turning fully clockwise.
(2)
Remove cap (10) from suction valve and cap (4) from discharge valve for access to
valve stems.
(3)
Close both suction and discharge valves by turning valve stems fully clockwise. This
will isolate the compressor from the rest of the system.
(4)
Slowly open the handwheel gauge port valves (1, 3) counterclockwise 1/2 to 1 turn.
This will allow the refrigerant to escape from the compressor and through the gauge
manifold.
(5)
Open the valve (5) on the empty container (6) by turning counterclockwise.
(6)
Start and run the portable vacuum pump (8).
(7)
While the vacuum pump is running, watch the pressure on the combination gauge (2).
When pressure has dropped to 1 or 2 psig on gauge (2), close hand wheel gauge port
valves (1, 3) and stop the vacuum pump. This will leave a slight positive charge on the
compressor.
(8)
If gauge pressure increases rapidly, repeat steps a.(5) through (8) above until 1 or 2
psig is maintained on combination gauge (2).
(9)
Close valve (5) on container (6) by turning fully clockwise.
WARNING
Purge hoselines before disconnecting. Residual freon in lines can cause personal
injury.
(10) Disconnect all manifold gauge hoselines (5, 6, 7, FIGURE 4-16).
WARNING
Purge hoselines before disconnecting. Residual freon in lines can cause personal
injury.
(11) Disconnect vacuum pump discharge line (7, FIGURE 4-18) from container (6).
4-59
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |