TM 55-1905-223-24-17
4-11. Replace/Repair Fan, Ventilating (Exhaust Fans 1 and 2). (FIGURE 4-1)
This task covers:
a. Removal
b. Disassembly
c. Repair
d. Assembly
e. Replcaement
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's
Service - Do Not Operate."
Tool kit, refrigeration and
See TM 55-1905-223-10 for HVAC SYSTEMS
air conditioning,
operation and equipment location.
Materials/Parts
Warning tags, Item 1, Appendix C
Ventilating fan P/N 65-35-AV03
Axial fan impeller P/N 656503500
REMOVAL
WARNING
Make sure electrical power is OFF to avoid personal injury.
a. Turn electrical power OFF.
b. Tag and disconnect electrical wiring to the fan.
c.
Remove plain hexnuts, lockwashers, and flat washers (2 and 13) and hexhead screws and flat
washers (3 and 12) from each end of the fan. This will disconnect the fan from the bell inlet (26) and
companion flange (14) at each end of the fan. The fan will also be disconnected from the mounting
feet (25) which hold the fan to the deck.
d. Remove the fan (1).
DISASSEMBLY
a. With the fan unit removed, disconnect outlet cone (15) from vane section (16) by removing plain
hexnut, lockwasher, and flat washer (11) and hexhead screw and flat washer (10).
4-18
|