Click here to make tpub.com your Home Page

Page Title: AIR CONDITIONING (Cont)
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 55-1905-223-24-17
Table 4-1. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
AIR CONDITIONING - CONT
19.
Partial or insufficient cooling - blower running.
STEP 1.
Check for low refrigerant charge. Find and repair leak. Evacuate, recharge system with R-
22 (Malfunction 10 and paragraph 4-10).
STEP 2.
Check for air in system. Purge (Malfunction 4). If purging is unsuccessful, remove charge,
or evacuate, and recharge with R-22 (paragraph 4-10).
STEP 3.
Check to see if wrong refrigerant is in the system.
a.
Make certain R-22 only was added to the system. If not, purge. If purging is not
successful, remove refrigerant, evacuate, and recharge with R-22 (paragraph 4-10).
b.
Purge non-condensables (A/C-2 only):
(1)
Stop compressor but allow seawater to continue passing through condenser. Allow
compressor to cool for 10 minutes.
WARNING
PRESSURIZED GAS. Open valve slowly to avoid rapid release of refrigerant gas.
Avoid contact with released gas and pressure.
(2)
Crack open the discharge (service) valve on the compressor very slowly (clockwise).
Allow only a small amount of vapor to be released for 2 seconds. Close the
discharge valve fully counterclockwise.
(3)
Start the compressor and check to see if the discharge pressure is still above 230
psig. If so, operate the compressor for 5 minutes and repeat the purging procedure.
Normally, purging 3 or 4 times will remove non-condensables.
4-12

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business