|
|
![]() TM 55-1905-223-24-17
Table 4-1. Troubleshooting - CONT
Malfunction
Test or Inspection
Corrective Action
AIR CONDITIONING - CONT
NOTE
The low pressure control solenoid must be bypassed to allow unit to operate below
normal pressure.
(8)
Watch the operating pressure on the combination (suction pressure) gauge.
When pressure has dropped to 2 inches of vacuum on the gauge, stop the
compressor. If the pressure rises rapidly, there is still residual refrigerant in the
compressor. Start compressor and again pump pressure down to 2 inches of
vacuum and stop compressor. If pressure remains at 1 or 2 inches of vacuum,
or rises very slowly, close the compressor discharge (service) valve fully
clockwise.
WARNING
Turn electrical power OFF.
(9)
If pressure remains in a vacuum, secure electrical power to the compressor
and crack the outlet valve from the receiver momentarily to introduce sufficient
refrigerant to obtain only a slight positive pressure of 1-2 psig to prevent air
from being sucked into the system when opened.
WARNING
Do not open system with pressure exceeding 2 psig on the combination (suction
pressure) gauge.
(10) When a slight positive pressure of 1-2 psig is maintained, the liquid line, low
pressure side of the system (including cooling coil/evaporator), and the
compressor can be opened for maintenance and service.
(11) When maintenance is completed, slowly open the refrigerant outlet- valve from
the receiver. Open the discharge (service) valve on the compressor fully
counterclockwise.
(12) Restore electrical power, start and run the air conditioner assembly to check
operation.
4-9
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |