TM 55-1905-223-24-17
(e) Remove the three mounting screws (1) and slide motor (3) out of housing (2).
(f) Remove mounting bracket (4) from motor (3).
(2) Replacement.
(a) Install mounting bracket (4) to motor (3).
(b) Align motor shaft with blower wheel on inside of housing (2).
Slide
motor
into
blower housing (2) and install mounting screws (1).
(c) Make sure the blower wheel is not rubbing against the housing. Tighten blower wheel
setscrew firmly on motor shaft.
(d) Install new capacitor (5).
(e) Install cable ties to mounting bracket in their original positions.
(f) Connect electrical wiring to proper terminals on capacitor (5) and motor (3).
d. Replace condensate pump (8) and motor (7) as follows:
(1) Tag and disconnect electrical wiring to electric pump motor (7).
(2) Disconnect pump (8) from drain piping.
(3) Remove the motor and pump assembly from the air conditioning unit.
(4) Remove pump (8) from motor (7).
(5) Install new pump to motor.
(6) Install pump and motor assembly.
(7) Connect pump (8) to drain piping.
(8) Connect electrical wiring to proper terminals on motor (7).
e. Replace high pressure switch (9) as follows:
(1) Remove switch cover.
(2) Tag and disconnect electrical wiring to switch.
(3) Remove switch from mounting.
(4) Install new switch (9).
(5) Connect electrical wiring to proper terminals.
(6) Install switch cover.
3-63
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |