TM 55-1905-223-24-17
3-21. Repair Fan, Ventilating (Supply Fan #5). (FIGURE 3-12)
This task covers:
a. Repair
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
See TM 55-1905-223-10 for HVAC systems
operation and equipment.
Materials/Parts
Tag, Item 1, Appendix C
Front box guard P/N 716654-01
Impeller P/N 603921-01
REPAIR
WARNING
Make sure electrical power is OFF to avoid personal injury.
a. Remove box guard (5) from ventilating fan (1) (paragraph 2-26).
b. Visually check the box guard (5) for dented guard material (6). Remove dents by bending or
hammering as necessary. Refer to paragraph 2-27 for removing and replacing guard.
c.
Visually check impeller (4) for bent or broken blades. Replace ventilating fan if blades are bent or
broken (paragraph 2-31).
d. For repair of ac motor, refer to paragraph 3-20.
e. Install guard (5) on ventilating fan (1) (paragraph 2-27).
f.
Operational check:
(1)
Turn electrical power ON.
(2)
Start and run fan to check operation.
(3)
Remove "Out of Service" tag from circuit.
3-49
|