3-19. Repair Fan, Ventilating (Supply Fan #4). (FIGURE 3-10)
This task covers:
a. Repair
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
See TM 55-1905-223-10 for HVAC systems
Materials/Parts
operation and equipment.
Tag, Item 1, Appendix C
Impeller P/N 783078-36
Bearings P/N 716625-03
Shaft P/N 717189-01
Grease lines P/N 716661-02
Bushings P/N 725539-14
Fan bushing P/N 725409-10
REPAIR
WARNING
Make sure electrical power is OFF to avoid personal injury.
a. Remove ventilating fan (paragraph 2-26).
b. Remove electric motor (1) and V-belt (19) from fan unit (paragraphs 2-26 thru 2-28).
c.
Replace grease lines (7):
(1)
Disconnect the two grease lines (7) on the inside and outside of fan drum (6).
(2)
Install new grease lines (7) to inside and outside fittings on fan drum (6).
d. Replace impeller (3), fan bushing (4), and machine key (16):
(1)
Remove impeller nosepiece (2).
(2)
Remove impeller (3) and machine key (16) from fan shaft (15).