3-17. Repair Fan, Ventilating (Supply Fan #3). (FIGURE 3-8)
This task covers:
a. Removal
b. Repair
c Replacement
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
See TM 55-1905-223-10 for HVAC systems
Materials/Parts
operation and equipment.
Tag, Item 1, Appendix C
Ventilating Fan P/N 44-12-DG2
Bushing P/N 402000010
Impeller P/N 6518700Z0
REMOVAL
WARNING
Make sure electrical power is OFF to avoid personal injury.
a. Turn power OFF.
b. Tag and disconnect electrical wiring to the fan.
c.
Remove mounting hardware (5, 6, 11, 12) from each end of the fan (1). This will disconnect the fan
from companion flange (7) on each end of ducting.
d. Remove the fan unit.
REPAIR
a. With the fan unit removed, disconnect the vane section (4) of the fan unit (1) by removing mounting
hardware (2, 3).
b. Remove the impeller (9) from the shaft of the motor (10).
c.
Remove the bushing (8) from the impeller (9).