TM 55-1905-223-24-17
3-14. Repair Heater, Space, Electric (Units #1, #2, #4, #9, #10, and #11). (FIGURE 3-5)
This task covers:
a. Repair
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
See TM 55-1905-223-10 for HVAC systems
Materials/Parts
operation and equipment location.
Tags, Item 1, Appendix C
Knob P/N 169-049278-001
Thermostat P/N 300-049197-003
Magnetic contactor
P/N 072-049587-015 (Units 1 and 2)
Magnetic contactor
P/N 072-052560-003 Units 4, 9, 10, and 11)
Thermostatic switch
P/N 300-049200-001
Alternating current motor
P/N 193-130381-007
(Units 1, 2, 4 and 10)
P/N 193-130381-002
Units 9 and 11)
REPAIR
WARNING
Make sure electrical power is OFF to prevent personal injury.
a.
Turn electrical power to heater (1) OFF.
b.
Replace thermostat and knob:
(1)
Remove knob (3) from front side of case (15).
3-27
|