TM 55-1905-223-24-17
3-12. Repair Heater, Duct Type, Stationary (Duct #2, #3, #17). (FIGURE 3-3)
This task covers:
a. Repair
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switched OFF, power
panel locked and tagged "Out of
Tool kit, electrician's,
Service - Do Not Operate."
See TM 55-1905-223-10 for HVAC systems
Materials/Parts
Operation and equipment location.
Tags, Item 1, Appendix C
Control contactor 52332002
(Ducts 2, 3, and 17)
Power transformer P/N 41017003
(Ducts 2, 3, and 17)
Manual limit capillary reset
P/N 41984011 (Ducts 2, 3, and 17)
Automatic limit capillary reset
P/N 50025003 (Ducts 2, 3, and 17)
Airflow switch P/N 51085002
(Ducts 2, 3, and 17)
Air probe P/N 41653001
(Ducts 2, 3, and 17)
REPAIR
WARNING
Make sure electrical power is OFF to avoid personal injury.
a.
Turn electrical power to heater OFF and open terminal box door (8).
b.
Replace control contactor (7):
(1)
Tag and disconnect electrical wiring from contactor.
(2)
Remove associated hardware and contactor (7) from terminal box (3).