2-36. Replace Condenser, Refridgerating Water Cooled...(FIGURE 2-28)
This task covers:
a. Removal
b.
Replacement
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switch OFF,
power panel locked and tagged
Tool kit, refrigeration and
"Out of Service - Do Not Operate."
air conditioning,
See TM 55-1905-223-10 for HVAC systems
operation and equipment locations.
Materials/Parts
Tag, Item 1, Appendix C
Condenser, Refrigerating
PN SW 18 3/4 M3 3/4
REMOVAL
WARNING
Make sure electrical power is OFF and circuit tagged out-of-
service.
a. Remove all refrigerant from system.
b. Close external seawater inlet valve to condenser.
c. Drain condenser and close external seawater outlet valve.
d. Disconnect (unsolder) the following lines from the condenser (1).
(1) Refrigerant inlet line connection (2).
(2) Seawater outlet line connection (3).
(3) Seawater inlet line connection (5).
(4) Refrigerant outlet line connection (6).
e. Cover the ends of piping with rags to keep dirt and debris from entering until condenser is installed.
2-105