TM 55-1905-223-24-17
2-35. Repair Motor, Electric (A/C #2, Accomodations)
This task covers:
a. Repair
INITIAL SETUP :
Tools
Equipment Condition
Tool kit, general mechanic's,
Circuit breaker switch OFF,
power panel locked and tagged
Tool kit, electrician's,
"Out of Service - Do Not Operate."
Belt guard and V-belt removed,
Puller, 5120-00-516-3120
Hydraulic Press PN 2009-13
Electric motor removed (para. 4-15).
Materials/Parts
See TM 55-1905-223-10 for HVAC systems
operation and equipment locations.
Tag, Item 1, Appendix C
Bearing P/N P4881
Bearing P/N P4879
REPAIR
Repair consists of replacing motor bearings.
WARNING
Make sure electrical power is OFF to avoid personal injury.
a. Use a puller and remove sheave (3, FIGURE 2-26) and key (2) from motor (1) shaft.
b. Remove four screws (6, FIGURE 2-27) and remove end cover (7).
c.
Remove four screws (8) and remove end cover (1).
d. Slide rotor (9) from motor housing (4).
e. Use a puller and remove bearings (5) and (6) from shaft.
f.
Use a hydraulic press and install new bearings (5) and (6) onto shaft.
g. Install key (2, FIGURE 2-26) and sheave (3) on shaft of motor (1).
2-101
|