|
|
TM 55-1905-223-24-17
d.
Condenser.
(1)
The condenser serves two important functions:
(a)
It removes the heat picked up by the refrigerant in the cooling coil.
(b)
It condenses the refrigerant vapor to a refrigerant liquid.
(2)
The heat removal and condensing processes take place by a water cooling process. The
refrigerant vapor is passed through an outer shell of the condenser tubes and cool seawater
passes through an inner shell, or tubing (FIGURE 1-4). The seawater supplied to the condenser
is at a lower temperature than the temperature of the refrigerant vapor. Heat from the refrigerant
is transferred to the seawater through the inner tubing walls. The seawater then carries the heat
from the condenser through a discharge or drain line. The condenser removes enough heat to
change the refrigerant from a vapor to a liquid.
e.
Expansion Valve. FIGURE 1-5 illustrates the principle of both the expansion valve method and
the capillary tube method of metering the refrigerant flow.
NOTE
The self-contained air conditioning units use a capillary tube assembly in the place
of an expansion valve. However, the principle, or function, of supplying refrigerant
to the cooling coil is the same in both methods.
(1)
Expansion Valve Method. The expansion valve reduces the pressure of the refrigerant liquid,
and in doing so, it cools the liquid. Refrigerant enters the valve under pressure. As it passes
through a small valve port, it enters the low pressure area of the cooling coil. The valve port acts
as a metering device between a high pressure area (the condenser), and a low pressure area (the
cooling coil). As the pressure is reduced, the point at which the liquid becomes a vapor is also
reduced. Therefore, after the liquid refrigerant passes through the metering port in the expansion
valve, it begins to vaporize in the cooling coil because it is now in a low pressure area.
(2)
Capillary Tube Method (Self-Contained A/C Units). The principle, or function, of the capillary
tube method is the same as that of the expansion valve method. The basic difference in the two
methods is that the refrigerant is metered through a series of long, small diameter capillary
tubes instead of through a single, small valve port. (See FIGURE 1-5.)
NOTE
The number of capillary tubes will vary in different types of air conditioners.
1-17
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |